Electronic thermal overload relay,TeSys Giga,57-225 A,class 5E-30E,push-in control connection

ELECTRONIC THERMAL OVERLOAD RE

SQDLR9G225 LR9G225 3606481912541
648.00 / EA
http://schema.org/OutOfStock
  • Depth: 126 mm
TeSys LR9G 225A thermal overload relay is compatible with TeSys Giga high power contactor, push-in control connection. It provides phase imbalance, phase failure, in-built ground-fault and single-phase loads protections. It is available for manual and auto reset options and LED indicator for Motor ON and pre-trip alarm. Tripping classes is selectable from class 5E to class 30E to suit different application needs from fast tripping, general purpose and high inertia loads. It is suitable for independent mounting or direct mounting with LC1G contactors. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature without derating up to 3000m altitude. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine). Unique QR code provides quick access to complete product data.
QTY
  • Product Description
  • Features
  • Specifications
TeSys LR9G 225A thermal overload relay is compatible with TeSys Giga high power contactor, push-in control connection. It provides phase imbalance, phase failure, in-built ground-fault and single-phase loads protections. It is available for manual and auto reset options and LED indicator for Motor ON and pre-trip alarm. Tripping classes is selectable from class 5E to class 30E to suit different application needs from fast tripping, general purpose and high inertia loads. It is suitable for independent mounting or direct mounting with LC1G contactors. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature without derating up to 3000m altitude. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine). Unique QR code provides quick access to complete product data.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Nickel (Metallic), which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Physical Attributes
    • Color : dark grey
  • Conformance Attributes
    • Product Certifications : CB Scheme, CCC, cULus, UKCA, ATEX, EU-RO-MR by DNV-GL, EAC
    • Standards : EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ, UL 60335-1
  • Complementary Attributes
    • Uc Control Circuit Voltage : 24...500 V AC 50/60 Hz, 24...250 V DC
    • Ue Rated Operational Voltage : 1000 V AC 50/60 Hz
    • Uimp Rated Impulse Withstand Voltage : 8 kV
  • Important Information Attributes
    • Persona Type Ids : EU, OM, OM8, PB
    • Persona Type Names : End User, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Electromagnetic Compatibility : EMC immunity conforming to IEC 60947-4-1, emission tests criteria A conforming to IEC 60947-4-1, immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3, voltage dips and interruptions immunity test conforming to SEMI F47
    • Local Signalling : LED, trip indicator
    • Mechanical Robustness : vibrations 5-300 Hz 6 gn contactor open, shocks 15 gn 11 ms contactor closed
    • Mounting Support : direct on contactor, plate
    • Network Frequency : 30...60 Hz, 100 Hz
    • Protection Type : phase imbalance 0-5 s - alarm circuit UL 60947-4-1, ground fault protection 0-1 s - alarm circuit IEC 60947-4-1, ground fault protection 0-1 s - alarm circuit UL 60947-4-1, phase loss 0-4 s - alarm circuit, phase imbalance 0-5 s - alarm circuit IEC 60947-4-1
    • Reset : automatic reset, manual
    • Connections Terminals : power circuit: bar - busbar cross section: 25 x 6 mm, power circuit: lugs-ring terminals 1 185-185 mm², control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end, control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end, control circuit: push-in 2 0.5-1.0 mm² with cable end
    • Carbon Footprint Of The Distribution Phase A4 : 0.2420705189143047, 0.2 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 2.380924036454045, 2 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0.1 kg CO2 eq., 0.050884093084178
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 15 kg CO2 eq., 14.8607648604244
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 206 kg CO2 eq., 205.7033000544477
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-03-26
    • Global Commercial Status : Commercialised
    • Return Indicator : Y
    • Stocking Flag : N
    • Stock Policy : 2
    • Device Type : Relay, Control & Measurement - Protection relay
    • Serviceability : No
    • Traceability : No
    • Service Catalog Item : Finished good
    • Legacy Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI2105014
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2121
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 7
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Tier Id : 1
    • Tier : 1
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Product Kit Identifier : N
    • Contacts Type And Composition : 1 NO + 1 NC
    • Device Short Name : LR9G
    • Halogen Free Status : Halogen free plastic parts product
    • Mechanical Durability : 7000 cycles
    • Network Type : AC
    • Overvoltage Category : III
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Name : TeSys LRG
    • Product Or Component Type : electronic thermal overload relay
    • Protective Treatment : TH
    • Range : TeSys
    • Relay Application : motor protection
    • Returnability : Yes
    • Software Version : v6.1
    • Sustainable Packaging : No
    • Thermal Overload Class : class 5E...30E IEC 60947-4-1
    • Thermal Protection Adjustment Range : 57-225 A
    • Tightening Torque : 18 N.m
    • Total Lifecycle Carbon Footprint : 223 kg CO2 eq.
    • Tripping Threshold : 1.125 +/- 0.07 In IEC 60947-4-1
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Ith Conventional Free Air Thermal Current : 5 A
    • Warranty In Months : 18
    • R Thermal Protection Adj Range : 57-225 A
    • Pep Code : ENVPEP2105014EN
    • Database Version : 2023-02
    • Pep Verification Date : 2025-08-05
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : referent product
    • Functional Unit Description : Other switchgear and controlgear solutions mentioned in the scope (e.g. fuses TC32, all-or-nothing relays TC94, Measuring relays and protection equipment TC95), apply the general rules of PCR and mention in the accompanying report the functional unit, the reference product characteristics, the reference lifetime and the use scenario which are applied consistently with the relevant IEC technical standards.
    • Functional Unit Quantity : 1
    • Functional Unit Unit : unit
    • Product Weight In G2 : 1600
    • Reference Lifetime In Y2 : 20
    • Energy Consumption On Product Lifetime In Kwh : 235.644
    • Energy Model Manufacturing A1 A3 2 : China, CN
    • Energy Model Installation A5 2 : Electricity Mix; Low voltage; 2018; China, CN
    • Energy Model Use B6 2 : Electricity Mix; Low voltage; 2018; China, CN
    • Energy Model End Of Life C1 C4 2 : Electricity Mix; Low voltage; 2018; China, CN
    • Recyclability Potential In 2 : 42
    • Offer Owner Code : 190788
    • Height Nominal : 107 mm
    • Width Nominal : 105 mm
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -25-60 °C, -25-60 °C
    • Ambient Air Transport Temperature : -25-60 °C, -25-60 °C
    • Ip Degree Of Protection : IP2X front face with shrouds IEC 60529, IP2X front face with shrouds VDE 0106
    • Permissible Ambient Air Temperature Around The Device : -40-60 °C at Uc, -40-60 °C at Uc, -40-60 °C at Uc, -40-60 °C at Uc
    • Take Back : Nej
    • Halogene Performance : Halogen free plastic parts product
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 223.23794356332465
    • Ambient Air Temperature For Storage : -60-80 °C
    • Circularity Profile : ENVEOLI2105014
    • Environmental Disclosure : ENVPEP2105014EN
    • Eu Rohs Directive : Compliant By Exemption
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP2105014EN
    • Pep Verification Date : 2025-08-05
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : electronic thermal overload relay
  • ETIM
    • ETIM 8 : EC000106
    • ETIM 9 : EC000106
  • Surge Protection And Filtering Attributes
    • Surge Withstand : 4 kV
  • Specifications
    • Depth : 126 mm