Capacitor contactor, TeSys Deca, 20 kVAR at 400 V/50 Hz, coil 220 V AC 50/60 Hz

CAPACITOR CONTACTOR, TESYS DEC

SQDLC1DLKM7 LC1DLKM7 3606480401824
725.52 / EA
http://schema.org/OutOfStock
  • Warranty Length: 18 mth
TeSys Deca contactor, 3 poles (3NO), for switching 3-phase capacitor banks up to 20kVAR@400V 50Hz (33kVAR@690V). It provides a 220V 50/60Hz AC coil, 1NO+2NC instantaneous auxiliary contacts, with front mounted early make poles and pre-wired damping resistors for current limitation. For operating rates until 240 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Certified IEC 60947 and compliant with shunt capacitors standard IEC 60831.
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca contactor, 3 poles (3NO), for switching 3-phase capacitor banks up to 20kVAR@400V 50Hz (33kVAR@690V). It provides a 220V 50/60Hz AC coil, 1NO+2NC instantaneous auxiliary contacts, with front mounted early make poles and pre-wired damping resistors for current limitation. For operating rates until 240 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Certified IEC 60947 and compliant with shunt capacitors standard IEC 60831.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Complementary Attributes
    • Control Circuit Type : AC 50/60 Hz
    • Maximum Operating Rate : 240 cyc/h
    • UC Control Circuit Voltage : 220 V AC 50/60 Hz
    • UE Rated Operational Voltage : power circuit 690 V AC 50/60 Hz
  • Important Information Attributes
    • Persona Type Ids : EU, LC, OM, OM8, PB, SI
    • Persona Type Names : End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, System Integrator
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Device Location In System : line interruption, inside delta interruption
    • Electrical Durability : 300000 cycles 400 V, 200000 cycles 690 V
    • Range : TeSys, TeSys Deca
    • Reactive Power Rating : 11 kvar 230-230 V AC 50 Hz 60 °C, 20 kvar 400-400 V AC 50 Hz 60 °C, 21 kvar 440-440 V AC 50 Hz 60 °C, 33 kvar 690-690 V AC 50 Hz 60 °C
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals, power circuit 2.5 N.m screw clamp terminals
    • Connections Terminals : control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 1 2.5-16 mm² - cable stiffness: solid, power circuit: screw clamp terminals 2 2.5-6 mm² - cable stiffness: solid, power circuit: screw clamp terminals 1 1.5-10 mm² - cable stiffness: flexible without cable end, power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible without cable end, power circuit: screw clamp terminals 1 1-10 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible with cable end
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-05-31
    • Device Type : LV equipment - LV contactor
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 20 year(s)
    • Legacy WEEE Scope : In
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : No need of specific recycling operations
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • ROHS EUR In Scope : Yes
    • ROHS EUR Status : Compliant
    • ROHS EUR Full Compliance Status : Compliant
    • ROHS EUR Full Compliance Status Id : COMPLIANT
    • China ROHS In Scope : No
    • Green Premium Status For Reporting : Green Premium product
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : N
    • WD Status : 1 - GSC certified
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Compatibility Code : LC1D
    • Contactor Application : power factor correction
    • Device Short Name : LC1DLK
    • Package Weight Lbs : 608 g
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : capacitor duty contactor
    • Range Of Product : TeSys Deca
    • Returnability : No
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 0 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Relationship Type : Compatible relationship
    • Pep Code : ENVPEP1112074EN
    • Pep Verification Date : 2025-06-17
    • PCR Version : PEP-PCR-ed4-2021 09 06
    • PSR Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
    • Functional Unit Description : Switch on and off during 20 years electrical power supply of a downstream installation with an electrical and/or mechanical control.The functional unit is characterized by a type Capacitor duty contactor, a control circuit voltage 220V, a power circuit voltage 690V and a rated operational current 200A.
    • Functional Unit Unit : Unit
    • Product Kit Identifier : N
    • Product Manager : NANNAN YAN
  • Environment Attributes Main
    • EU ROHS Directive : Compliant​, Compliant
    • ROHS Exemption Information : Yes
    • Take Back : No
    • Reach Free SHVC : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • China ROHS Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 0
    • Environmental Disclosure : ENVPEP1112074EN
    • IP Degree Of Protection : IP20 front face IEC 60529
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of SVHC : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP1112074EN
    • Pep Verification Date : 2025-06-17
    • PCR Version : PEP-PCR-ed4-2021 09 06
    • PSR Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : capacitor duty contactor
    • Range Of Product : TeSys Deca
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months