TeSys D IEC contactor, 40 A, 3 P, 30 HP at 480 VAC, nonreversing, 120 VAC 50/60 Hz coil

IEC CONTACTOR 40A/3P/120V COIL

SQDLC1D40G7 LC1D40G7 3389110948561
411.10 / EA
http://schema.org/OutOfStock
  • Country of Origin: Czechia
  • Depth: 119 mm
  • Height: 127 mm
  • Net Weight: 1.4 kg
  • Warranty Length: 18 mth
  • Weight: 1.4 kg
  • Width: 75 mm
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 40A/690V AC-3 (18.5kW@400V). They can be used to create motor starters for almost any type of application. It provides a 120V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (75mm width), DIN-rail mounting or screw fixing. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 40A/690V AC-3 (18.5kW@400V). They can be used to create motor starters for almost any type of application. It provides a 120V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (75mm width), DIN-rail mounting or screw fixing. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Product Certifications : DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
    • Net Weight : 1.4 kg
    • Flame Retardance : V1 conforming to UL 94
    • Operating Altitude : 9842.52 ft (3000 m) without derating
    • Width : 75 mm
    • Depth : 119 mm
    • Permissible Ambient Air Temperature Around The Device : -5-60 °C || -40-70 °C at Uc
    • Height : 127 mm
    • Standards : UL 508 || IEC 60947-4-1 || CSA C22.2 No 14 || EN 60947-4-1 || IEC 60947-5-1 || EN 60947-5-1
    • Climatic Withstand : IACS E10 exposure to damp heat
    • Ip Degree Of Protection : IP2X IEC 60529 || IP2X VDE 0106
    • Mechanical Robustness : shocks contactor opened 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
    • Fire Resistance : 850 °C IEC 60695-2-1
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Mercury Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Minimum Percentage Of Recycled Plastic Content : 0
    • Take-Back : No
    • Sustainable Packaging : Yes
    • Global Warming ; Total Life Cycle​ : 56 kg CO2 eq.
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 56.01010576
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP110205EN
    • Packaging Without Single Use Plastic : Yes
    • Toxic Heavy Metal Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : N/A
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
    • Minimum Switching Current : 5 mA for control circuit
    • Power Dissipation Per Pole : 5.4 W AC-1 || 2.4 W AC-3
    • Average Impedance : 1.5 mOhm - Ith 60 A 50 Hz for power circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • Mounting Support : rail || plate
    • Insulation Resistance : > 10 MOhm for control circuit
    • Inrush Power In Va : 140-140 VA cos phi 0.75 (at 20 °C) || 160-160 VA cos phi 0.75 (at 20 °C)
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
    • Pole Contact Composition : 3 NO
    • Connections - Terminals : control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 1 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 2 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminal 1 2.5-35 mm² - cable stiffness: solid with cable end || power circuit: screw clamp terminal 2 2.5-35 mm² - cable stiffness: solid with cable end || power circuit: screw clamp terminal 1 2.5-35 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminal 2 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminal 1 2.5-35 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminal 2 2.5-35 mm² - cable stiffness: flexible with cable end
    • Coil Technology : without built-in bidirectional peak limiting diode suppressor
    • Maximum Operating Rate : 3600 cyc/h at 60 °C
    • Auxiliary Contacts Type : mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1
    • Hold-In Power Consumption In Va : 13-13 VA 50 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 60 Hz cos phi 0.3 (at 20 °C)
    • Overvoltage Category : III
    • Maximum Horse Power Rating : 10 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to CSA || 10 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to UL || 10 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to CSA || 10 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to UL || 3 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA || 3 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL || 30 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to CSA || 30 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to UL || 30 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to CSA || 30 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to UL || 5 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA || 5 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL
    • Motor Power Kw : 18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 22 kW at 1000 V AC 50/60 Hz (AC-3) || 22 kW at 415 V AC 50/60 Hz (AC-3) || 22 kW at 440 V AC 50/60 Hz (AC-3) || 22 kW at 500 V AC 50/60 Hz (AC-3) || 30 kW at 660...690 V AC 50/60 Hz (AC-3) || 11 kW at 220...230 V AC 50/60 Hz (AC-3) || 9 kW at 400 V AC 50/60 Hz (AC-4)
    • [Ui] Rated Insulation Voltage : control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
    • Protective Cover : with
    • [Ith] Conventional Free Air Thermal Current : 10 A (at 60 °C) for control circuit || 60 A (at 60 °C) for power circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc (60-60 °C):drop-out AC 50/60 Hz || 0.8...1.1 Uc (60-60 °C):operational AC 50 Hz || 0.85...1.1 Uc (60-60 °C):operational AC 60 Hz
    • Control Circuit Type : AC 50/60 Hz
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Rated Breaking Capacity : 800 A at 440 V for power circuit conforming to IEC 60947
    • Irms Rated Making Capacity : 140 A AC for control circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
    • Associated Fuse Rating : 10 A gG for control circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
    • Operating Time : 12...26 ms closing || 4...19 ms opening
    • Minimum Switching Voltage : 17 V for control circuit
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm || power circuit 5 N.m screw clamp terminal flat Ø 8 mm
    • Mechanical Durability : 6000000 cycles
    • Compatibility Code : LC1D
    • Heat Dissipation : 4-5 W at 50/60 Hz for control circuit
  • Specifications
    • Country of Origin : Czechia
    • Width : 75 mm
    • Height : 127 mm
    • Weight : 1.4 kg
    • [Uc] Control Circuit Voltage : 120 V AC 50/60 Hz
    • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
    • Contactor Application : resistive load || motor control
    • Product Or Component Type : contactor
    • Utilisation Category : AC-3 || AC-4 || AC-1 || AC-2
    • [Ie] Rated Operational Current : 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    • Poles Description : 3P
    • Range Of Product : TeSys Deca
    • Range : TeSys
    • Device Short Name : LC1D