Contactor, high power, TeSys Giga, standard version, 3 pole/NO, AC-3 <=440V 185A, 100-250VAC/DC coil

HIGH POWER CONTACTOR, TESYS GI

SQDLC1G185KUEN LC1G185KUEN 3606481921949
1279.80 / EA
http://schema.org/OutOfStock
  • Country of Origin: France
  • Depth: 193 mm
  • Height: 193 mm
  • Net Weight: 3.5 kg
  • Weight: 3.5 kg
  • Width: 108 mm
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 185A 110kW@440V. It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine). Unique QR code provides quick access to complete product data.
QTY
  • Product Description
  • Features
  • Specifications
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 185A 110kW@440V. It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine). Unique QR code provides quick access to complete product data.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Complementary
    • Product Certifications : CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
    • Power Dissipation Per Pole : 20 W AC-1 - Ith 305 A || 6 W AC-3 - Ith 185 A
    • Average Impedance : 0.00017 Ohm
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • Mounting Support : plate
    • Hold-In Power Consumption In W : 7.8-7.8 W
    • Net Weight : 3.5 kg
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV
    • Inrush Power In Va : 540-540 VA
    • Pole Contact Composition : 3 NO
    • Connections - Terminals : power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end
    • Coil Technology : built-in bidirectional peak limiting
    • Maximum Operating Rate : 600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
    • Mechanical Durability : 8 Mcycles
    • Hold-In Power Consumption In Va : 12.4-12.4 VA
    • Width : 108 mm
    • Overvoltage Category : III
    • Depth : 193 mm
    • Maximum Horse Power Rating : 50 hp at 200/208 V 60 Hz || 60 hp at 230/240 V 60 Hz || 125 hp at 460/480 V 60 Hz || 150 hp at 575/600 V 60 Hz
    • Motor Power Kw : 55 kW at 230 V AC 50/60 Hz (AC-3e) || 90 kW at 400 V AC 50/60 Hz (AC-3e) || 90 kW at 415 V AC 50/60 Hz (AC-3e) || 110 kW at 440 V AC 50/60 Hz (AC-3e) || 110 kW at 500 V AC 50/60 Hz (AC-3e) || 110 kW at 690 V AC 50/60 Hz (AC-3e) || 75 kW at 1000 V AC 50/60 Hz (AC-3e) || 55 kW at 230 V AC 50/60 Hz (AC-3) || 90 kW at 400 V AC 50/60 Hz (AC-3) || 90 kW at 415 V AC 50/60 Hz (AC-3) || 110 kW at 440 V AC 50/60 Hz (AC-3) || 110 kW at 500 V AC 50/60 Hz (AC-3) || 110 kW at 690 V AC 50/60 Hz (AC-3) || 75 kW at 1000 V AC 50/60 Hz (AC-3) || 55 kW at 230 V AC 50/60 Hz (AC-4) || 90 kW at 400 V AC 50/60 Hz (AC-4) || 90 kW at 415 V AC 50/60 Hz (AC-4) || 100 kW at 440 V AC 50/60 Hz (AC-4) || 110 kW at 500 V AC 50/60 Hz (AC-4) || 110 kW at 690 V AC 50/60 Hz (AC-4) || 75 kW at 1000 V AC 50/60 Hz (AC-4)
    • [Ui] Rated Insulation Voltage : 1000 V
    • Inrush Power In W : 380 W
    • Height : 193 mm
    • Connection Pitch : 35 mm
    • [Ith] Conventional Free Air Thermal Current : 305 A (at 40 °C)
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
    • Safety Reliability Level : B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Rated Breaking Capacity : 1610 A at 440 V
    • Irms Rated Making Capacity : 2310 A at 440 V
    • Associated Fuse Rating : 200 A aM at <= 440 V for motor || 160 A aM at <= 690 V for motor || 315 A gG at <= 690 V
    • Operating Time : 40...70 ms closing || 15...50 ms opening
    • Tightening Torque : 18 N.m
    • Compatibility Code : LC1G
    • [Icw] Rated Short-Time Withstand Current : 1.5 kA - 10 s || 0.92 kA - 30 s || 0.74 kA - 1 min || 0.5 kA - 3 min || 0.4 kA - 10 min
  • Specifications
    • Country of Origin : France
    • Width : 108 mm
    • Height : 193 mm
    • Weight : 3.5 kg
    • [Uc] Control Circuit Voltage : 100...250 V AC 50/60 Hz || 100...250 V DC
    • Contactor Application : power switching || motor control
    • Product Or Component Type : contactor
    • Utilisation Category : AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
    • [Ie] Rated Operational Current : 305 A (at <40 °C) at <= 1000 V AC-1 || 185 A (at <60 °C) at <= 440 V AC-3
    • Poles Description : 3P
    • Range Of Product : TeSys Giga
    • Control Circuit Voltage Limits : operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
    • Range : TeSys
    • Device Short Name : LC1G
  • Environmental data
    • Mercury Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Minimum Percentage Of Recycled Plastic Content : 0
    • Take-Back : No
    • Global Warming ; Total Life Cycle​ : 763 kg CO2 eq.
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 763.3432797033329
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP2105013
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Without Single Use Plastic : No
    • Scip Number : 6fbdad13-bb7c-47d4-a6d6-d82dd6f54349
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI2105013
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant with Exemptions
  • Environment
    • Permissible Ambient Air Temperature Around The Device : -40-70 °C at Uc
    • Ambient Air Temperature For Operation : -25-60 °C
    • Ambient Air Temperature For Storage : -60-80 °C
    • Protective Treatment : TH
    • Ip Degree Of Protection : IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
    • Mechanical Robustness : vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
    • Color : dark grey