Electronic time delay auxiliary contact block, TeSys K, 1C/O, on delay 1-30s, front, control 110...240V AC

CONTACTOR TIMED CONTACTS

SQDLA2KT2U LA2KT2U 3389110230086
93.97 / EA
http://schema.org/OutOfStock
  • Country of Origin: Tunisia
  • Depth: 38 mm
  • Height: 27 mm
  • Net Weight: 0.04 kg
  • Warranty Length: 18 mth
  • Weight: 0.04 kg
  • Width: 38 mm
TeSys K electronic time delay contact block, for contactors LC.K, LP.K, CA.K. It provides 1C/O contact rated up to 2A 240V AC, with an on-delay setting range 1-30s. To be used for contactors with 110-240V AC/DC coils (F7 to U7, FD to UD). Front mounting by clip-on, connections by attached wires to the contactor. It conforms to RoHS/REACh regulation.
QTY
  • Product Description
  • Specifications
TeSys K electronic time delay contact block, for contactors LC.K, LP.K, CA.K. It provides 1C/O contact rated up to 2A 240V AC, with an on-delay setting range 1-30s. To be used for contactors with 110-240V AC/DC coils (F7 to U7, FD to UD). Front mounting by clip-on, connections by attached wires to the contactor. It conforms to RoHS/REACh regulation.
  • Environment
    • Ambient Air Temperature For Operation : -10-60 °C
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Environmental Characteristic : normal environment
    • Protective Treatment : TC IEC 60068
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP2106022
    • Packaging Without Single Use Plastic : Yes
    • Scip Number : 8a21c0d1-be95-4e83-b703-1e8075e942f8
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : N/A
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 2.6248757
  • Complementary
    • Height : 27 mm
    • Insulation Resistance : > 10 MOhm
    • Net Weight : 0.04 kg
    • Connections - Terminals : slip-on terminals
    • Reset Time : 1.5 s during time delay || 0.5 s after time delay
    • Width : 38 mm
    • Depth : 38 mm
  • Specifications
    • Country of Origin : Tunisia
    • Width : 38 mm
    • Height : 27 mm
    • Weight : 0.04 kg
    • Product Certifications : CE || UKCA
    • [Ith] Conventional Free Air Thermal Current : 2 A for signalling circuit
    • Timer Type : on delay
    • Rated Operational Voltage Limits : 0.85...1.1 Uc
    • [Ue] Rated Operational Voltage : 110...240 V AC control circuit || 240 V AC signalling circuit
    • Standards : EN/IEC 60947-5-1
    • Range Compatibility : TeSys K LC1K || TeSys K CA2K || TeSys K CA3K || TeSys K CA4K
    • Product Or Component Type : time delay auxiliary contact block
    • Product Name : TeSys K
    • Range : TeSys
    • Mounting Location : front
    • Pole Contact Composition : 1 C/O
    • Time Delay Range : 1...30 s
    • Auxiliary Contacts Operation : time delay
    • Device Short Name : LA1