PowerPact B-Frame Molded Case Circuit Breakers Unit Mount - BJL36080LU

MOLDED CASE CIRCUIT BRKR 600Y/

SQDBJL36080LU BJL36080LU 360648114975
0.00 / EA
  • Color: Gray
  • Mounting Type: By Screws Plate || Clip-on 35 Mm Symmetrical DIN Rail
  • Package Weight: 2.600 lbs
  • Storage Temperature: -58° To 185 °F (-50° To 85 °C)
  • Voltage: 690 V
PowerPact B circuit breakers – efficiency that clicks.
  • Product Description
  • Additional Information
PowerPact B circuit breakers – efficiency that clicks.
  • Features
    • Applications
      • Industrial Control Panels
      • Commercial OEM
      • Electrical Distribution Equipment
      • Commercial Buildings
      • Industrial Buildings
    • Saves time in electrical design, mounting, and wiring. With integrated DIN rail mounting and built-in control wire terminals, your work clicks right into place.
    • Tackles last minute changes. When they come up, be ready with one-click field installable accessories and the industry’s widest range of operating mechanisms.
    • Provides fast startup and fewer call-backs. EverLink lugs combat cable creep and deliver a durable, long-term connection.
  • Specifications
    • Main
      • Range : PowerPact
      • Product Name : PowerPact B
      • Device Short Name : BJ 080
      • Product Or Component Type : Circuit breaker
      • Device Application : Distribution
    • Complementary
      • Line Rated Current : 80 A
      • Poles Description : 3P
      • Protected Poles Description : 3t
      • Control Type : Toggle
      • Mounting Mode : By screws plate || Clip-on 35 mm symmetrical DIN rail
      • Network Type : AC
      • Network Frequency : 50/60 Hz
      • Breaking Capacity Code : J
      • Breaking Capacity : 100 kA at 240 V AC 50/60 Hz according to UL 489 || 65 kA at 480 V AC 50/60 Hz according to UL 489 || Icu: 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2 || Icu: 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2 || Icu: 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2 || Icu: 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2 || Icu: 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2 || 65 kA at 480Y/277 V AC 50/60 Hz according to UL 489 || 25 kA at 600Y/347 V AC 50/60 Hz according to UL 489 || 100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
      • System Voltage : 690 V AC 50/60 Hz according to IEC 60947-2
      • Rated Service Breaking Capacity : 100 kA: at 220...240 V AC 50/60 Hz according to IEC 60947-2 || 65 kA: at 380...415 V AC 50/60 Hz according to IEC 60947-2 || 65 kA: at 440 V AC 50/60 Hz according to IEC 60947-2 || 25 kA: at 500...525 V AC 50/60 Hz according to IEC 60947-2 || 10 kA: at 690 V AC 50/60 Hz according to IEC 60947-2
      • Rated Impulse Withstand Voltage : 8 kV according to IEC 60947-2
      • Rated Insulation Voltage : 800 V according to IEC 60947-2
      • Trip Unit Technology : Thermal-magnetic
      • Trip Unit Name : TM-D
      • Trip Unit Protection Functions : LI
      • Protection Type : Overload protection (thermal) || Short-circuit protection (magnetic)
      • Trip Unit Rating : 80 A at 104 °F (40 °C)
      • Magnetic Hold Current : 800 A
      • Magnetic Tripping Current : 1200 A
      • Suitability For Isolation : Yes according to IEC 60947-2
      • Utilisation Category : Category A
      • Mechanical Durability : 15000 cycles IEC 947-1 Annex K ed 5.2
      • Electrical Durability : 10000 cycles according to IEC 947-1 Annex K ed 5.2 In at 440 V
      • Connection Pitch : 1.06 in (27 mm)
      • Local Signalling : Green flag presence of auxiliary contacts
      • Rotary Handle Padlocking : Padlock in OFF or ON position
      • Connections - Terminals : Upside 1 EverLink lug with voltage tap-off wire size 0...0.11 in² (2.5...70 mm²) (AWG 14...AWG 2/0) , fine stranded copper || Downside 1 Everlink lug wire size 0...0.11 in² (2.5...70 mm²) (AWG 14...AWG 2/0) , fine stranded copper || Upside 1 EverLink lug with voltage tap-off wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/copper || Downside 1 Everlink lug wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/copper
      • Current Of Common : 10 A 0...0.01 in² (0.5...6 mm²) ( AWG 20...AWG 10) , (stranded or fine stranded) || 10 A 0...0.01 in² (1.5...6 mm²) ( AWG 20...AWG 10) , (rigid)
      • Tightening Torque : 44.25 lbf.in (5 N.m) 0...0.02 in² (2.5...16 mm²) (AWG 14...AWG 4) || 79.65 lbf.in (9 N.m) 0.04...0.15 in² (25...95 mm²) (AWG 3...AWG 3/0)
      • Number Of Slots : 1 slot(s) auxiliary switch OF (plug-in) || 1 slot(s) voltage release MN or MX (plug-in) || 1 slot(s) alarm switch SD (plug-in)
      • Wire Stripping Length : 0.79 in (20 mm)
      • Quality Labels : CE
      • Standards : EN/IEC 60947-5-1 || EN/IEC 60947-2 || NEMA AB1 || CSA C22.2 No 5 || UL 489 || GB 14048.2 || NMX J-266
      • Colour : Grey (RAL 7016)
      • 9 mm Pitches : 9
      • Height : 5.39 in (137 mm)
      • Width : 3.19 in (81 mm)
      • Depth : 3.15 in (80 mm)
      • Product Weight : 2.37 lb(US) (1.074 kg)
      • Quantity Per Set : Set of 1
    • Environment
      • Product Certifications : UL || CSA || CCC || EAC || NOM || IEC
      • IP Degree Of Protection : IP40 (front cover) according to IEC 60529
      • IK Degree Of Protection : IK07 according to IEC 62262
      • Pollution Degree : 3 according to IEC 60947-1
      • Ambient Air Temperature For Operation : -13° To 158 °F (-25° To 70 °C)
      • Ambient Air Temperature For Storage : -58° To 185 °F (-50° To 85 °C)
      • Operating Altitude : 5000 m with derating || 6561.68 ft (2000 m) without derating
    • Ordering and Shipping Details
      • Category : 01132 - BJ/BK UNIT MOUNT BREAKER/SWITCH
      • Discount Schedule : DE2
      • GTIN : 003606481149756
      • Number Of Units In Package : 1
      • Package Weight(Lbs) : 2.6000000000000001
      • Returnability : N
      • Country Of Origin : US
    • Offer Sustainability
      • Sustainable Offer Status : Green Premium product
      • RoHS (Date Code: YYWW) : Compliant  - since  1644  -  Schneider Electric declaration of conformity
      • Product Environmental Profile : Available
      • Product End Of Life Instructions : Need no specific recycling operations