NEMA Control Relay, Type X, machine tool, 10A resistive at 600 VAC, 2 normally open contacts, 24 VAC 60 Hz coil

NEMA Control Relay, Type X, machine tool, 10A resistive at 600 VAC, 2 normally open contacts, 24 VAC 60 Hz coil

SQD8501XO20V01 8501XO20V01 785901536932
145.98 / EACH
  • Certifications: CSA LR60905 Class 3211 03, UL Listed File E78403 CCN NKCR
  • Depth: 3.95 in
  • Height: 3.5 in
  • Line Rated Current: 10 A, 5 A
  • Warranty Length: 18 mth
  • Width: 2.23 in
8501X NEMA machine tool relays combine a rugged heavy duty design with modular construction for greater flexiblity. They are ideal for applications where long life, high reliability and ease of maintenance are important. This relay has contacts with a 10 ampere resistive current rating at 600 VAC. The contacts also have an A600 inductive contact rating. This relay is supplied with two 8501XC1 contact cartridges. The contact cartridges are installed as normally open contacts. The machine tool relays have straight through wiring. This makes wiring easier. The two plug in contact cartridges in this relay make contact conversion or replacement very easy. Contact conversion or replacement can be done without removing any wiring. Contacts are supplied with pressure wire connectors so wires can be easily terminated. 18 to 12 AWG copper wire can be used with this relay. Relay has a 24 VAC 60 VAC replaceable coil. Relay is UL listed and CSA certified. Relay is UL listed and CSA certified.
  • Product Description
  • Specifications
8501X NEMA machine tool relays combine a rugged heavy duty design with modular construction for greater flexiblity. They are ideal for applications where long life, high reliability and ease of maintenance are important. This relay has contacts with a 10 ampere resistive current rating at 600 VAC. The contacts also have an A600 inductive contact rating. This relay is supplied with two 8501XC1 contact cartridges. The contact cartridges are installed as normally open contacts. The machine tool relays have straight through wiring. This makes wiring easier. The two plug in contact cartridges in this relay make contact conversion or replacement very easy. Contact conversion or replacement can be done without removing any wiring. Contacts are supplied with pressure wire connectors so wires can be easily terminated. 18 to 12 AWG copper wire can be used with this relay. Relay has a 24 VAC 60 VAC replaceable coil. Relay is UL listed and CSA certified. Relay is UL listed and CSA certified.
  • [Uc] Control Circuit Voltage : 24 V AC 60 Hz
  • Inrush Power In Va : 148-148 VA 60 Hz
  • Contacts Type And Composition : 2 NO 2 standard contact cartridges
  • Mounting Support : panel
  • Range Of Product : 8501X
  • Hold-In Power Consumption In Va : 23-23 VA 60 Hz
  • [Icm] Rated Short-Circuit Making Capacity : 60 A 120 V AC inductive control circuit UL 508 || 0.8 A 250 V DC resistive control circuit UL 508 || 30 A 240 V AC inductive control circuit UL 508 || 15 A 480 V AC inductive control circuit UL 508 || 12 A 600 V AC inductive control circuit UL 508 || 10 A <= 600 V AC resistive control circuit UL 508 || 1.1 A 125 V DC inductive control circuit UL 508 || 0.55 A 250 V DC inductive control circuit UL 508 || 0.2 A 301...600 V DC inductive control circuit UL 508 || 4 A 125 V DC inductive control circuit UL 508
  • Product Or Component Type : relay
  • Electrical Connection : screw clamp terminals
  • Awg Gauge : AWG 18...AWG 12 copper
  • Rated Breaking Capacity : 6 A 120 V AC inductive control circuit UL 508 || 0.8 A 250 V DC resistive control circuit UL 508 || 3 A 240 V AC inductive control circuit UL 508 || 1.5 A 480 V AC inductive control circuit UL 508 || 1.2 A 600 V AC inductive control circuit UL 508 || 10 A <= 600 V AC resistive control circuit UL 508 || 1.1 A 125 V DC inductive control circuit UL 508 || 0.55 A 250 V DC inductive control circuit UL 508 || 0.2 A 301...600 V DC inductive control circuit UL 508 || 4 A 125 V DC resistive control circuit UL 508
  • Maximum Width : 2.23 in
  • Maximum Height : 3.5 in
  • Product Certifications : CSA LR60905 class 3211 03 || UL listed file E78403 CCN NKCR
  • Control Circuit Voltage Limits : operational 0.85...1.1 Uc AC 60 Hz
  • Warranty : 18 months
  • Tightening Torque : control circuit 1.02-1.36 N.m screw terminals
  • Line Rated Current : 10 A AC || 5 A DC
  • Ambient Air Temperature For Operation : -40-160 °F
  • Maximum Depth : 3.95 in
  • Operating Time : 15 ms - pick-up || 16 ms - drop-out
  • Relay Type : control