SQUARE D

Guard switch, Telemecanique Safety switches XCS, XCSTR, spindle 80 mm, 2NC+1 NO, M16

Guard switch, Telemecanique Sa

SQDXCSTR762 T3389110177282
0.00 / EA
http://schema.org/OutOfStock
  • Certifications: BG, CSA, UL
  • Chain/Cable Diameter: 7-10 mm
  • Depth: 110 mm
  • Enclosure Material: Polyamide PA66 Fibre Glass Impregnated
  • Height: 117-117 mm
  • IsSustainable: No
  • Material: Plastic
  • Net Weight: 0.187 kg
  • Number of Poles: 3
  • Standard: CSA C22.2 No 14, EN 1088/ISO 14119, EN/IEC 60204-1, EN/IEC 60947-5-1, EN/IEC 60947-5-4, EN/ISO 12100, UL 508
  • Storage Temperature: -40-70 °C
  • Warranty Length: 18 mth
  • Width: 52 mm
QTY
  • Specifications
  • Specifications
    • Contacts Type And Composition : 1 NC + 1 NC + 1 NO
    • Range Of Product : Telemecanique Safety switches XCS
    • Cable Entry : 2 entries tapped M16 x 1.5
    • Clamping Connection Capacity : 1 x 0.34...2 x 0.75 mm² with or without cable end
    • Product Or Component Type : guard switch
    • Component Name : XCSTR
    • Material : plastic
    • Head Type : turret head rotary axis
    • Insulation : double insulated
    • Contact Operation : slow-break, break before make
    • Type Of Operator : spindle 80 mm
    • Electrical Connection : terminal
    • Number Of Poles : 3
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Height : 117-117 mm
    • Short-Circuit Protection : 6 A cartridge fuse gG (gl)
    • Minimum Actuation Speed : 0.1 m/s
    • [Ithe] Conventional Enclosed Thermal Current : 6 A
    • Lever Material : stainless steel
    • Tripping Angle : 5 °
    • Net Weight : 0.187 kg
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV EN/IEC 60947-5-1
    • [Ui] Rated Insulation Voltage : 300 VUL 508 || 300 VCSA C22.2 No 14 || 400 V 3)EN/IEC 60947-1
    • Positive Opening : with NC contact
    • Positive Opening Minimum Torque : 0.45 N.m
    • Mechanical Durability : 1000000 cycles
    • Safety Reliability Data : B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
    • Enclosure Material : polyamide PA66 fibre glass impregnated
    • Contact Code Designation : B300, AC-15 (Ue = 120 V, Ie = 6 A)EN/IEC 60947-5-1 || B300, AC-15 (Ue = 240 V, Ie = 3 A)EN/IEC 60947-5-1 || Q300, DC-13 (Ue = 125 V, Ie = 0.2 A)EN/IEC 60947-5-1 || R300, DC-13 (Ue = 250 V, Ie = 0.1 A)EN/IEC 60947-5-1
    • Width : 52 mm
    • Depth : 110 mm
    • Cable Outer Diameter : 7-10 mm
    • Minimum Torque For Tripping : 0.1 N.m
    • Maximum Resistance Across Terminals : 30 mOhm EN/IEC 60947-5-4
    • Safety Level : can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach SIL 3 with the appropriate monitoring system and correctly wired IEC 61508
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP110606EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI110603EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Environment
    • Product Certifications : UL || CSA || BG
    • Ambient Air Temperature For Operation : -25-70 °C
    • Standards : EN/IEC 60947-5-1 || EN/ISO 12100 || CSA C22.2 No 14 || EN/IEC 60947-5-4 || UL 508 || EN/IEC 60204-1 || EN 1088/ISO 14119
    • Shock Resistance : 50 gn 11 ms IEC 60068-2-27
    • Vibration Resistance : 50 gn 10-500 Hz)IEC 60068-2-6
    • Ip Degree Of Protection : IP67 conforming to IEC 60529
    • Ambient Air Temperature For Storage : -40-70 °C
    • Electrical Shock Protection Class : class II EN/IEC 61140
    • Protective Treatment : TC || TH