Electronic pressure sensors, Pressure sensors XM, transmitter, XMEP, 250 bar, G1/4 A male, 4...20 mA, M12, set of 1

ELECTRONIC PRESSURE SENSORS, P

SQDXMEP250BD21F TSQDXMEP250BD21F
0.00 / EA
http://schema.org/OutOfStock
  • Certifications: CE, CULus, E2
  • Current: 23 mA
  • Diameter: 26 mm
  • Length: 38.1 mm
  • Net Weight: 0.095 kg
  • Standard: ECE 10R-5, EN 13309, EN/IEC 61326-2-3, ISO 13766, ISO 14982, UL 61010-1
  • Storage Temperature: -50-100 °C
QTY
  • Specifications
  • Specifications
    • Pressure Sensor Type : pressure transmitter
    • Type Of Output Signal : analogue
    • Range Of Product : Telemecanique Pressure sensors XM
    • Electrical Connection : 1 male connector M12 4 pins
    • Product Or Component Type : electronic pressure sensors
    • Type Of Packing : individual
    • Local Display : without
    • Pressure Sensor Name : XMEP
    • Current Consumption : < 23 mA
    • Fluid Connection Type : G 1/4A (male) DIN 3852-E
    • Pressure Sensor Size : 250 bar
    • Analogue Output Function : 4...20 mA, 2-wire
    • Controlled Fluid : fresh water 0-125 °C) || air -30-125 °C) || hydraulic oil -30-125 °C)
    • Quantity Per Set : set of 1
    • Electrical Circuit Type : control circuit
    • [Us] Rated Supply Voltage : 12...24 V DC SELV 9-36 V)
  • Complementary
    • Accuracy : 0.1 % of the measuring range
    • Diameter : 26 mm
    • [Uimp] Rated Impulse Withstand Voltage : 0.5 kV
    • Repeat Accuracy : +/- 0.5 % of the measuring range
    • Drift Of The Zero Point : +/- 0.02 % of measuring range/°K
    • Electromagnetic Compatibility : electrostatic discharge immunity test ISO 10605 criteria A 15 kV air, 15 kV contact || susceptibility to electromagnetic fields ISO 11452-2 criteria A 100 V/m 200…2000 MHz || susceptibility to electromagnetic fields ISO 11452-4 criteria A 100 mA 20…400 MHz || susceptibility to conducted disturbances EN/IEC 61000-4-6 criteria A 30 V 0.15...80 MHz || electrical fast transient/burst immunity test EN/IEC 61000-4-4 criteria A 4 kV || susceptibility to conducted transient disturbances ISO 7637-2 criteria B level 3
    • Materials In Contact With Fluid : stainless steel AISI 316L || fluorocarbon FPM
    • Length : 38.1 mm
    • Net Weight : 0.095 kg
    • Mechanical Durability : 10000000 cycles
    • Operating Position : any position
    • Measurement Accuracy : +/- 0.5 % of the measuring range
    • Protection Type : load short-circuit || reverse polarity
    • Drift Of The Sensitivity : +/- 0.02 % of measuring range/°K
    • Maximum Permissible Accidental Pressure : 750 bar
    • Destruction Pressure : 1500 bar
    • Response Time On Output : <= 2 ms 10...90 % of full scale
    • Pressure Setting Range : 0-250 bar
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1511013EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Environment
    • Product Certifications : CE || cULus || E2
    • Ambient Air Temperature For Operation : -40-100 °C
    • Standards : EN 13309 || EN/IEC 61326-2-3 || ISO 14982 || ISO 13766 || ECE 10R-5 || UL 61010-1
    • Shock Resistance : 50 gn 11 ms EN/IEC 60068-2-27
    • Vibration Resistance : 12 gn sinus 20-520 Hz) test 4 ISO 16750-3 || 18 gn random 10-2000 Hz) test 4 ISO 16750-3
    • Ip Degree Of Protection : IP65 conforming to EN/IEC 60529 || IP67 conforming to EN/IEC 60529 || IP69K conforming to EN/IEC 60529
    • Ambient Air Temperature For Storage : -50-100 °C