Multi9 - C60H-DC - MCB - 2P - 40 A - B Curve - 500 V DC - 10 kA

Multi9 - C60H-DC - MCB - 2P - 40 A - B Curve - 500 V DC - 10 kA

SQDM9U11240 M9U11240 785901773832
232.46 / EA
  • Amperage: 40 A
  • Certifications: CCC, IEC, UR
  • Country of Origin: China
  • Depth: 2.87 in, 73 mm
  • Height: 3.19 in, 81 mm
  • Mounting Type: Clip-On
  • Standard: EN/IEC 60947-2, GB 14048.2, UL 1077
  • Strip Length: 0.55 in, 14 mm
  • Voltage: 220 V, 440 V, 500 V
  • Weight: 0.128 kg, 0.28 lb
  • Width: 1.42 in, 36 mm
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 2P circuit breaker with 2 protected poles, 40A rated current and B tripping curve. The rated short circuit breaking capacity goes up to 20kA at 220VDC conforming to EN/IEC 60947-2 standard and 20kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
  • Product Description
  • Specifications
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 2P circuit breaker with 2 protected poles, 40A rated current and B tripping curve. The rated short circuit breaking capacity goes up to 20kA at 220VDC conforming to EN/IEC 60947-2 standard and 20kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
  • Ordering And Shipping Details
    • Nbr. Of Units In Pkg. : 1
    • Category : 00948 - M9 GEN 2 CB UL1077 / IEC
    • Returnability : No
    • GTIN : 00785901773832
    • Country Of Origin : CN
    • Discount Schedule : DE2
  • Environment
    • IP Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
    • Tropicalisation : 2 IEC 60068-2 || 2 GB 14048.2
    • Pollution Degree : 3 EN/IEC 60947-2
    • Relative Humidity : 95 % 131 °F (55 °C)
    • Ambient Air Temp For Storage : -40…185 °F (-40…85 °C)
    • Heat Dissipation : 8.6 W 440 V - 40 A
    • Ambient Air Temp For Op : -13…158 °F (-25…70 °C)
  • Complementary
    • Tightening Torque : 30.98 lbf.in (3.5 N.m) top or bottom
    • Uimp Rated Imp Wstd Voltage : 6 kVEN/IEC 60947-2
    • Electrical Durability : 3000 cycles 250 V DC L/R = 2 ms || 6000 cycles 250 V DC
    • Wire Stripping Length : 0.55 in (14 mm) top or bottom
    • Width : 1.42 in (36 mm)
    • 9 mm Pitches : 4
    • Earth-Leakage Protection : Without
    • Contact Position Indicator : Yes
    • Connections - Terminals : Tunnel type terminal top or bottom) 0.00…0.05 in² (1…35 mm²) AWG 18...AWG 2) - rigid stranded || Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) AWG 18...AWG 4) - flexible || Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) AWG 18...AWG 4) - flexible with ferrule || Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…16 mm²) AWG 18...AWG 6) - rigid stranded || Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…16 mm²) AWG 18...AWG 6) - flexible || Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…16 mm²) AWG 18...AWG 6) - flexible with ferrule || Tunnel type terminal top or bottom) - 3 0.01 in² (4 mm²) AWG 6) - flexible stranded
    • Product Weight : 0.28 lb(US) (0.128 kg)
    • Ics Rated Service Breaking Cap : 7.5 kA 75 % EN/IEC 60947-2 - 440 V DC || 4.5 kA 75 % EN/IEC 60947-2 - 500 V DC || 15 kA 75 % EN/IEC 60947-2 - 220 V DC || 7.5 kA 75 % GB 14048.2 - 440 V DC || 4.5 kA 75 % GB 14048.2 - 500 V DC || 15 kA 75 % GB 14048.2 - 220 V DC
    • Provision For Padlocking : Padlockable
    • Control Type : Toggle
    • Ue Rated Operational Voltage : 220 V DC || 440 V DC || 500 V DC
    • Height : 3.19 in (81 mm)
    • Depth : 2.87 in (73 mm)
    • Magnetic Tripping Limit : 3…7 x In DC
    • Ui Rated Insulation Voltage : 500 V DC EN/IEC 60947-2
    • Mounting Support : DIN rail
    • Mounting Mode : Clip-on
    • Colour : Gray
    • Mechanical Durability : 20000 cycles
    • Local Signalling : ON/OFF indication
  • Offer Sustainability
    • EU RoHs Directive : Compliant
    • Mercury Free : Yes
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • REACh Free Of SVHC : Yes
    • Toxic Heavy Metal Free : Yes
  • Main
    • Product Certifications : IEC || CCC || UR
    • Device Short Name : C60H-DC
    • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 1077
    • Product Or Component Type : Miniature circuit-breaker
    • Range : Multi 9
    • Curve Code : B
    • Number Of Protected Poles : 2
    • Trip Unit Technology : Thermal-magnetic
    • Product Name : Multi 9 C60H-DC
    • Utilisation Category : Category A EN/IEC 60947-2
    • Network Type : DC
    • Device Application : Distribution
    • Suitability For ISOlation : Yes EN/IEC 60947-2
    • Poles Description : 2P
    • In Rated Current : 40 A 77 °F (25 °C) EN/IEC 60947-2
    • Breaking Capacity : 20 kA Icu 220 V DC EN/IEC 60947-2 || 10 kA Icu 440 V DC EN/IEC 60947-2 || 6 kA Icu 500 V DC EN/IEC 60947-2 || 5 kA AIR 12...500 V DC UL 1077 || 20 kA Icu 220 V DC GB 14048.2 || 10 kA Icu 440 V DC GB 14048.2 || 6 kA Icu 500 V DC GB 14048.2