Schneider Electric at Mayer

Multi9 - C60H-DC - MCB - 1P - 25 A - B Curve - 250 V DC - 10 kA

Multi9 C60H-DC 25A B 250V-DC M

SQDM9U11125 M9U11125 785901772835
102.44 / EA
  • Certifications: CCC, IEC, UR
  • Depth: 73 mm
  • Height: 81 mm
  • Line Rated Current: 25 °C, 25 A
  • Mounting Type: Clip-On
  • Net Weight: 0.128 kg
  • Standard: EN/IEC 60947-2, GB 14048.2, UL 1077
  • Storage Temperature: -40-85 °C
  • Strip Length: 14 mm
  • Width: 18 mm
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 1P circuit breaker with 1 protected pole, 25A rated current and B tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VDC conforming to EN/IEC 60947-2 standard and 10kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 250VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
  • Product Description
  • Specifications
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 1P circuit breaker with 1 protected pole, 25A rated current and B tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VDC conforming to EN/IEC 60947-2 standard and 10kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 250VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
  • Control Type : toggle
  • [Ics] Rated Service Breaking Capacity : 7.5 kA 75 % EN/IEC 60947-2 - 220 V DC || 4.5 kA 75 % EN/IEC 60947-2 - 250 V DC || 15 kA 75 % EN/IEC 60947-2 - 110 V DC || 7.5 kA 75 % GB 14048.2 - 220 V DC || 4.5 kA 75 % GB 14048.2 - 250 V DC || 15 kA 75 % GB 14048.2 - 110 V DC
  • Mechanical Durability : 20000 cycles
  • Mounting Support : DIN rail
  • Poles Description : 1P
  • [Ue] Rated Operational Voltage : 250 V DC || 110 V DC || 220 V DC
  • Maximum Depth : 73 mm
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • Number Of Protected Poles : 1
  • Breaking Capacity Code : H
  • Magnetic Tripping Limit : 3…7 x In DC
  • Breaking Capacity : 10 kA Icu 220 V DC EN/IEC 60947-2 || 6 kA Icu 250 V DC EN/IEC 60947-2 || 20 kA Icu 110 V DC EN/IEC 60947-2 || 5 kA AIR 12...250 V DC UL 1077 || 10 kA Icu 220 V DC GB 14048.2 || 6 kA Icu 250 V DC GB 14048.2 || 20 kA Icu 110 V DC GB 14048.2
  • Trip Unit Technology : thermal-magnetic
  • [Ui] Rated Insulation Voltage : 500 V DC EN/IEC 60947-2
  • Maximum Width : 18 mm
  • Range Of Product : Multi 9
  • Electrical Durability : 3000 cycles 250 V DC L/R = 2 ms || 6000 cycles 250 V DC
  • Pollution Degree : 3 EN/IEC 60947-2
  • Earth-Leakage Protection : without
  • Range : Multi 9
  • Line Rated Current : 25 A 25 °C EN/IEC 60947-2
  • Ambient Air Temperature For Operation : -25-70 °C
  • Maximum Height : 81 mm
  • Network Type : DC
  • Product Or Component Type : miniature circuit-breaker
  • Wire Stripping Length : 14 mm top or bottom
  • Local Signalling : ON/OFF indication
  • Device Application : distribution
  • Tightening Torque : 3.5-3.5 N.m top or bottom
  • Product Certifications : IEC || CCC || UR
  • Color : Gray
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Ambient Air Temperature For Storage : -40-85 °C
  • Provision For Padlocking : padlockable
  • Device Short Name : C60H-DC
  • Utilisation Category : category A EN/IEC 60947-2
  • Heat Dissipation : 3.1-3.1 W 220 V - 25 A
  • Mounting Mode : clip-on
  • 9 Mm Pitches : 2
  • Curve Code : B
  • Tropicalisation : 2 IEC 60068-2 || 2 GB 14048.2
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Connections - Terminals : tunnel type terminal top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid stranded || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible with ferrule || tunnel type terminal top or bottom) - 2 1-16 mm² AWG 18...AWG 6) - rigid stranded || tunnel type terminal top or bottom) - 2 1-16 mm² AWG 18...AWG 6) - flexible || tunnel type terminal top or bottom) - 2 1-16 mm² AWG 18...AWG 6) - flexible with ferrule || tunnel type terminal top or bottom) - 3 4-4 mm² AWG 6) - flexible stranded
  • Net Weight : 0.128 kg
  • Product Name : Multi 9 C60H-DC
  • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 1077
  • Relative Humidity : 95-95 % 55-55 °C
  • Contact Position Indicator : yes