Bus bar, Linergy, 30 tap offs, 160A, 600VAC 50/60HZ, 160ALG664MM

26"" BUSBAR"

SQDAK5JB146 AK5JB146 3389110588989
329.69 / EA
http://schema.org/OutOfStock
  • Certifications: CSA, DNV, LROS (Lloyds Register Of Shipping), UL
  • Depth: 82 mm
  • Net Weight: 1.3 kg
  • Standard: IEC 60439
  • Warranty Length: 18 mth
  • Width: 81 mm
Busbars can be screw-mounted onto any type of support. If the busbar is to be used with component mounting plates with a tap-off, it is essential that the bus bar is mounted on the AM1DL201 DIN mounting rail. This 4 conducor bus bar system has 30 tap offs at 18 mm intervals. The busbar system is 26.3 inches (668 mm) long. Bus bar system is rated 160 A at 600 VAC. The bus bar system is 26.30 inches long, 3.19 inches wide and 3.23 inches deep. Each wieghs 0.41 oz. The busbar system is UL Listed, CSA certified and meet IEC requirements.
QTY
  • Product Description
  • Specifications
Busbars can be screw-mounted onto any type of support. If the busbar is to be used with component mounting plates with a tap-off, it is essential that the bus bar is mounted on the AM1DL201 DIN mounting rail. This 4 conducor bus bar system has 30 tap offs at 18 mm intervals. The busbar system is 26.3 inches (668 mm) long. Bus bar system is rated 160 A at 600 VAC. The bus bar system is 26.30 inches long, 3.19 inches wide and 3.23 inches deep. Each wieghs 0.41 oz. The busbar system is UL Listed, CSA certified and meet IEC requirements.
  • Environment
    • Product Certifications : LROS (Lloyds register of shipping) || DNV || UL || CSA
    • Standards : IEC 60439
    • Ip Degree Of Protection : IPxx B conforming to IEC 60529
    • Fire Resistance : 850 °C IEC 60695
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP120206EN
    • Sustainable Offer Status : Green Premium product
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Circularity Profile : N/A
    • Eu Rohs Directive : Compliant
  • Complementary
    • Bar Width : 45 mm
    • Network Frequency : 50/60 Hz
    • Protection Type : aM fuses In = 160 A, Isc = 100 kA, Ie = 160 A || gF fuses In = 160 A, Isc = 100 kA, Ie = 160 A || NS160H circuit breaker In = 160 A, Isc = 36 kA, Ie = 160 A || NS160H circuit breaker In = 160 A, Isc = 70 kA, Ie = 160 A
    • Connections - Terminals : connector 2.5-70 mm² flexible with cable end || connector 2.5-70 mm² rigid
    • Net Weight : 1.3 kg
    • Mounting Position : vertical using side stop AK5BT01 on mounting plates AK5PA || horizontal
    • Flame Retardance : V0 conforming to UL 94
    • [Ui] Rated Insulation Voltage : 600 V CSA || 600 V UL || 690 V IEC 60439-1
    • Tightening Torque : 10 N.m
    • Width : 81 mm
    • Depth : 82 mm
    • I²T On Activation : 10000000 A².s
    • Peak Current : 25 kA
  • Specifications
    • [Ue] Rated Operational Voltage : 400 V off-load plugging-in and unplugging, with supply switched on)IEC 60439-1 || 480 V off-load plugging-in and unplugging, with supply switched on)CSA || 480 V off-load plugging-in and unplugging, with supply switched on)UL || 600 V plugging-in and unplugging, with supply switched off)CSA || 600 V plugging-in and unplugging, with supply switched off)UL || 690 V plugging-in and unplugging, with supply switched off)IEC 60439-1
    • Network Type : AC
    • Product Or Component Type : busbar
    • Bar Length : 668 mm
    • Product Name : HK
    • Range : Linergy
    • Enclosure/Cubicle Width : 800 mm
    • [Ie] Rated Operational Current : 160 A 35 °C
    • Number Of Tap-Offs : 30
    • Number Of Conductors : 4
    • Device Application : distribution