Certifications:
CSA, IEC, UL Listed
-
Depth:
5.84 in
-
Height:
11 in
-
Line Rated Current:
300 A
-
Mounting Type:
Unit Mount
-
Trip Point:
3000-3000 A
-
Warranty Length:
18 mth
-
Width:
6 in
Square D LA molded case circuit breakers provide thermal magnetic protection. Their primary function is automatic opening of a circuit under overload or short circuit conditions or manual opening. LA circuit breakers contain thermal (overload) and magnetic (short circuit) sensing elements in each pole. Push-to-Trip allows the circuit breaker to be manually tripped without exposure to live parts. This Square D LA molded case circuit breaker is a 3 pole unit mount breaker, 300A and 600VAC. The thermal magnetic circuit breaker has an interrupting rating of 22kA for 600VAC and 10kA for 250VDC. The circuit breaker MB suffix indicates a panel main breaker and has a shorter handle so that the panel door can close. LA breakers are UL 489, CSA, IEC certified.