controller, Modicon MCM, 8 inputs 2 outputs, monitors expansion modules, screw

CONTROLLER 8 INPUT 2 OUTPUT

SQDXPSMCMCP0802 XPSMCMCP0802 3606480748561
430.51 / EA
http://schema.org/OutOfStock
  • Certifications: CULus, RCM, TÜV
  • Depth: 114.5 mm
  • Height: 99 mm
  • Net Weight: 0.25 kg
  • Number of Outputs: 2, 4
  • Standard: EN/IEC 61496-1, EN/IEC 61508, EN/IEC 61800-5-1, EN/ISO 13849-1, IEC 62061
  • Storage Temperature: -20-85 °C
  • Width: 22.5 mm
This Modicon MCM safety controller CPU is supplied with 24Vdc, has 8 safe digital inputs, 2 start/restart interlock inputs, 2 output OSSD pairs, 4 test outputs and 2 status outputs and is fitted with captive screw clamp terminals. It embeds a Mini USB 2.0 connector to receive the configuration done with the software EcoStruxure Machine Expert - HVAC. It is an appropriate solution for machines with a small number of safety functions requiring the configuration flexibility of a safety controller. It can be used as standalone or with fourteen expansion modules. The system is expandable up to 128 inputs, 16 outputs and up to 32 diagnostic status outputs, ideal for machines requiring multiple safety function monitoring. This safety controller CPU figures LEDs on its front face, displaying the status (power supply, run, internal or external errors, inputs status, communication, master enable, restart signal, output channels). It is a CPU with a rated supply voltage of 24V DC and a maximum power dissipation of 3W. It is furnished with spring clamp terminals, removable terminal block for electrical connection. It is an IP20 rated product. It weighs 0.25kg. Its dimension are 22.5mm (Depth), 99mm (Height) and 114.5mm (Width). Its housing is red. It is powered with 24 VDC. It is ideal for monitoring safety functions such as emergency stop, guard monitoring, perimeter guarding, position monitoring, speed monitoring and enabling movement. The safe controller CPU Modicon MCM are certified by TüV SÜD meeting the industrial safety standards of Category 4, PL e according to EN/ISO 13849-1 and SILCL 3 according to IEC/EN 61508 and IEC/EN 60261. Compatible accessories for Modicon MCM module are a memory card and the backplane connector. The safety controller CPU instals on Omega 35mm DIN rail conforming to EN 50022. The Modicon MCM modular safety controller system provide flexibility and scalability from 8 inputs, 2 dual/4 single channel outputs up to 128 inputs, 16 dual/32 single channel outputs, up to 32 or 48 diagnostic status outputs. Modicon MCM modular safety controller system are designed to monitor multiple safety functions on and around a machine to minimise the risk of people accessing the dangerous moving parts of the machine.
QTY
  • Product Description
  • Specifications
This Modicon MCM safety controller CPU is supplied with 24Vdc, has 8 safe digital inputs, 2 start/restart interlock inputs, 2 output OSSD pairs, 4 test outputs and 2 status outputs and is fitted with captive screw clamp terminals. It embeds a Mini USB 2.0 connector to receive the configuration done with the software EcoStruxure Machine Expert - HVAC. It is an appropriate solution for machines with a small number of safety functions requiring the configuration flexibility of a safety controller. It can be used as standalone or with fourteen expansion modules. The system is expandable up to 128 inputs, 16 outputs and up to 32 diagnostic status outputs, ideal for machines requiring multiple safety function monitoring. This safety controller CPU figures LEDs on its front face, displaying the status (power supply, run, internal or external errors, inputs status, communication, master enable, restart signal, output channels). It is a CPU with a rated supply voltage of 24V DC and a maximum power dissipation of 3W. It is furnished with spring clamp terminals, removable terminal block for electrical connection. It is an IP20 rated product. It weighs 0.25kg. Its dimension are 22.5mm (Depth), 99mm (Height) and 114.5mm (Width). Its housing is red. It is powered with 24 VDC. It is ideal for monitoring safety functions such as emergency stop, guard monitoring, perimeter guarding, position monitoring, speed monitoring and enabling movement. The safe controller CPU Modicon MCM are certified by TüV SÜD meeting the industrial safety standards of Category 4, PL e according to EN/ISO 13849-1 and SILCL 3 according to IEC/EN 61508 and IEC/EN 60261. Compatible accessories for Modicon MCM module are a memory card and the backplane connector. The safety controller CPU instals on Omega 35mm DIN rail conforming to EN 50022. The Modicon MCM modular safety controller system provide flexibility and scalability from 8 inputs, 2 dual/4 single channel outputs up to 128 inputs, 16 dual/32 single channel outputs, up to 32 or 48 diagnostic status outputs. Modicon MCM modular safety controller system are designed to monitor multiple safety functions on and around a machine to minimise the risk of people accessing the dangerous moving parts of the machine.
  • Environment
    • Product Certifications : cULus || RCM || TÜV
    • Ambient Air Temperature For Operation : -10-55 °C
    • Standards : EN/IEC 61508 || EN/ISO 13849-1 || EN/IEC 61496-1 || EN/IEC 61800-5-1 || IEC 62061
    • Pollution Degree : 2
    • Electromagnetic Compatibility : electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to EN/IEC 61000-4-2 || electrostatic discharge immunity test - test level: 20 kV (on air) conforming to EN/IEC 61000-4-2 || susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to EN/IEC 61000-4-3 || susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
    • Shock Resistance : 10 gn 16 ms) 1000 shocks on each axis EN/IEC 61496-1
    • Vibration Resistance : +/-0.35 mm 10-55 Hz)EN/IEC 61496-1
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV EN/IEC 61800-5-1
    • Ip Degree Of Protection : IP20
    • Relative Humidity : 10-95 %
    • Ambient Air Temperature For Storage : -20-85 °C
    • Service Life : 20 year(s)
    • Safety Reliability Data : PFHd = 6.06E-9 1/h || DC > 99 % || MTTFd < 100 years high
    • Overvoltage Category : II
    • Insulation : 250 V AC between power supply and housing EN/IEC 61800-5-1
  • Complementary
    • Connections - Terminals : 2 captive screw terminals, removable terminal block || 1 captive screw terminals, removable terminal block
    • Height : 99 mm
    • Integrated Connection Type : backplane expansion bus || USB 2.0 port
    • Cable Cross Section : 0.2-1.5 mm² - AWG 24...AWG 16 flexible without cable end || 0.2-2.5 mm² - AWG 24...AWG 14 flexible without cable end || 0.25-1 mm² - AWG 23...AWG 18 flexible with cable end, without bezel || 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, with bezel || 0.25-1.5 mm² - AWG 23...AWG 16 flexible with cable end, without bezel || 0.5-1.5 mm² - AWG 20...AWG 16 flexible with cable end, with double bezel || 0.2-1 mm² - AWG 24...AWG 18 solid without cable end || 0.2-2.5 mm² - AWG 24...AWG 14 solid without cable end
    • Local Signalling : 1 LED green PWR power ON || 1 LED green RUN RUN (status) || 1 LED red E IN internal error || 1 LED red E EX external error || 1 LED orange COM communication || 1 LED blue EN master enable || 8 LEDs yellow IN input status || 2 LEDs green/red OUT output status || 2 LEDs yellow RST restart signal || 2 LEDs yellow STATUS output channel
    • Maximum Number Of I/O Expansion Module : 14 128 input || 14 16 output
    • Net Weight : 0.25 kg
    • Power Dissipation In W : 3 W
    • Quality Labels : CE
    • Mounting Support : omega 35 mm DIN rail EN 50022
    • Load Capacitance : 0.82 µF
    • Width : 22.5 mm
    • Inductive Load : 30 mH
    • Depth : 114.5 mm
    • Synchronisation Time Between Inputs : < 0.5 ms
    • Data Storage Equipment : SD card optional)
    • Safety Level : can reach category 4 EN/ISO 13849-1 || can reach PL = e EN/ISO 13849-1 || type 4 EN/IEC 61496-1 || SILCL 3 IEC 62061
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1409010EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : X
    • Circularity Profile : ENVEOLI1409010EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Specifications
    • Discrete Output Type : PNP
    • Discrete Input Type : safety input || PNP
    • Range Of Product : Modicon Safety automation
    • Discrete Input Voltage : 24 V
    • Number Of Outputs : 2 safety outputs OSSD contactor/drive connection || 4 test line control outputs || 2 configurable diagnostic connection
    • Product Or Component Type : safety controller CPU
    • Discrete Input Current : 400 mA
    • Number Of Inputs : 8 digital input connection || 2 digital interlock start/restart or external device monitoring
    • [Us] Rated Supply Voltage : 24 V - 20...20 % DC
    • Electrical Connection : screw terminal
    • Discrete Output Current : 400 mA
    • Function Of Module : emergency stop EN/ISO 13850 || guard monitoring EN/ISO 14119 || enabling switch monitoring EN/IEC 60947-5-1 || light curtain monitoring EN/IEC 61496-1 || foot switch monitoring EN/IEC 60947-5-1 || magnetic switch monitoring EN/ISO 14119 || two-hand control EN 574 || safety mat monitoring EN/ISO 14119 || enabling switch monitoring EN 61326-1 || muting function of light curtains EN/IEC 60947-5-1 || counter functions EN/IEC 61800-5-2 || speed monitoring EN/IEC 61800-5-2
    • Device Short Name : XPSMCM